PEC Cable Sizing: A Worked Example, Step by Step

A concrete walkthrough of sizing a branch circuit cable under the Philippine Electrical Code — from design current to the final, derated recommendation.

Formulas are easier to trust once you've walked through a real example. Here's how a branch circuit cable actually gets sized under the Philippine Electrical Code, using the same logic as the OhmWorks PEC Cable Sizing calculator.

The Scenario

ParameterValue
Load current25 A, continuous
Installation methodConduit, 3 current-carrying conductors
Ambient temperature35°C
Run length22 meters, one-way
System voltage230V, single-phase

Step 1 — Establish the Design Current

For a continuous load, a safety margin is applied before anything else. This protects the conductor from a load that runs at or near full current for hours at a time, not just an instantaneous peak.

Step 2 — Pull Base Ampacity from the Table

The applicable PEC ampacity table gives a base current rating for each conductor size, keyed to insulation type and installation method — this is the starting point before any derating is applied.

Step 3 — Apply Derating

Two corrections get multiplied against that base rating: an ambient temperature factor (since 35°C is above the table's standard reference), and a grouping factor (since three current-carrying conductors share the conduit). The result is the conductor's real, derated ampacity in this specific installation — usually meaningfully lower than the table's headline number.

Step 4 — Check Voltage Drop

Separately, the 22-meter run length gets checked against the code's voltage drop limit at the design current. On a longer run like this, voltage drop can easily overtake ampacity as the limiting factor — which is exactly why both checks matter, not just the one that's easier to eyeball.

Step 5 — Take the Larger of the Two

Whichever check — derated ampacity or voltage drop — demands the bigger conductor determines the final size. This is the same four-step logic running behind every result in the calculator.

Every real project has its own load, length, and installation method — run your actual numbers in the PEC Cable Sizing calculator rather than treating this worked example as a substitute.